LOADPRO AFDD RCBO 1 MODULE

Main Features

Meets the requirements of BSEN 62606 & BSEN 61009-1 Single Pole and Switch Neutral configuration
Complete protection: RCBO & AFDD in one device
LED indication of various faults

Overcurrent and short circuit protection
Single module: Type A
6kA Rated breaking capacity
Rated voltage 240V and rated frequency 50Hz Maximum cable termination capacity is 25mm2 Maximum terminal torque is 2Nm

Current Rating (A)

Sensitivity (mA)

B Type Product Code

C Type Product Code

6 30 MAR1PB0630A MAR1PC0630A
10 30 MAR1PB1030A MAR1PC1030A
16 30 MAR1PB1630A MAR1PC1630A
20 30 MAR1PB2030A MAR1PC2030A
32 30 MAR1PB3230A MAR1PC3230A
40 30 MAR1PB4030A MAR1PC4030A
Technical Data
Rated voltage 240VAC
Rated residual operating current 30mA
Rated frequency 50Hz
Type A
Tripping characteristics B,C
Rated short-circuit capacity 6kA
Rated impulse withstand voltage 4kV
Energy Limiting Class 3
Number of poles 1P+N (1 module)
Type of trip Electronic
Mechanical endurance 10,000
Electrical endurance 1200
Degree of protection IP20
Ambient temperature -25 ~ +40 °C
Supply possibility Top or bottom
Installation 35mm DIN rail
Terminal capacity 25mm2
DATA-SHEET-LOADPRO-AFDD-RCBO-1-MODULE-6
DATA-SHEET-LOADPRO-AFDD-RCBO-1-MODULE-5
DATA-SHEET-LOADPRO-AFDD-RCBO-1-MODULE-4
DATA-SHEET-LOADPRO-AFDD-RCBO-1-MODULE-4
DATA-SHEET-LOADPRO-AFDD-RCBO-1-MODULE-4
DATA-SHEET-LOADPRO-AFDD-RCBO-1-MODULE-4

Datasheets

Boards

Standard Boards & RCCB Incomer

Split Boards

Single RCCB Board, Duel RCCB Boards & High Integrity Board

Devices

Incoming Devices

Switch Disconnector

RCCB + Accessory

Outgoing Devices

Single Pole MCBs

Single Pole RCBOs

Accessories

Modular Contractors

Metering

Surge Protection

Modular Programmable Timer